Thermal Reports/Blog/Thermography in Substations: Transformer and Busbar Inspection
    TermografiaSubestaçõesTransformadoresManutenção Preditiva

    Thermography in Substations: Transformer and Busbar Inspection

    Equipe Thermal Reports··7 min read
    Thermography in Substations: Transformer and Busbar Inspection

    Introduction

    Electrical substations are critical points in the power distribution system. They concentrate high-voltage equipment such as transformers, busbars, circuit breakers, disconnect switches and insulators — components whose failure can cause prolonged outages, significant material damage and safety risks.

    Infrared thermography is an essential tool for predictive maintenance in substations, making it possible to identify hot spots, defective connections and damaged insulators before they escalate into catastrophic failures.

    This technical guide presents the fundamentals of thermographic inspection in substations, critical equipment, fault patterns and severity criteria that take the measurement conditions into account.

    Electrical substation
    Electrical substation

    High-voltage electrical substation. Photo: Enric Cruz López / Pexels

    Why Use Thermography in Substations?

    Advantages of Thermographic Inspection

    1. Remote inspection — safety in high-voltage environments

    2. Early detection — identifies problems before failure

    3. No interruption — equipment remains energized

    4. Broad coverage — an inspection route covering accessible equipment

    5. Visual documentation — thermal history for trend analysis

    6. Maintenance prioritization — severity classification guides interventions

    Limitations and Precautions

    • Safety distance — respect the controlled zone and the risk zone
    • Weather conditions — wind, rain and fog affect measurements
    • Electrical load — equipment must be under representative load
    • Emissivity — metal surfaces reflect radiation from external sources
    • Visual access — a direct line of sight to critical components is required

    Critical Equipment in Substations

    1. Power Transformers

    Inspection points:

    • High- and low-voltage bushings
    • Input and output connections
    • On-load tap changer (OLTC)
    • Radiators and cooling system
    • Tank and conservator

    Common anomalies:

    • Heating in bushings (defective internal connection)
    • Hot spots on radiators (compromised oil circulation)
    • Heating in the tap changer (worn contacts)
    • Elevated tank temperature (overload or cooling failure)

    Assessment:

    The priority of the finding must take into account load, manufacturer limits, measurement quality, thermal history and equipment criticality. Document the reference used for comparison and the technical justification for the proposed action. This article does not establish universal temperature ranges or repair deadlines.

    2. Busbars

    Inspection points:

    • Connections between sections
    • Expansion joints
    • Connections to equipment
    • Supports and insulators

    Common anomalies:

    • Loose or oxidized connections
    • Corrosion at joints
    • Circuit overload
    • Phase imbalance

    Assessment:

    The priority of the finding must take into account load, manufacturer limits, measurement quality, thermal history and equipment criticality. Document the reference used for comparison and the technical justification for the proposed action. This article does not establish universal temperature ranges or repair deadlines.

    Substation busbars
    Substation busbars

    Busbars and insulators in a substation. Photo: Diana ✨ / Pexels

    3. Insulators

    Types:

    • Porcelain insulators
    • Polymer insulators
    • Through bushings

    Inspection points:

    • Insulator surface
    • Metal connections
    • Hardware fittings

    Common anomalies:

    • Electrical tracking
    • Surface contamination
    • Cracks or mechanical damage
    • Heating in hardware fittings

    Characteristic thermal pattern:

    • Normal insulator: ambient temperature
    • Tracking: localized heating along a line or at a point
    • Contamination: diffuse surface heating

    4. Circuit Breakers and Disconnect Switches

    Inspection points:

    • Main contacts
    • Input and output connections
    • Operating mechanism
    • Arc extinguishing chamber

    Common anomalies:

    • Worn or oxidized contacts
    • Loose connections
    • High contact resistance
    • Inadequate lubrication of the mechanism

    Criteria:

    5. Surge Arresters

    Inspection points:

    • Surge arrester body
    • Ground connections
    • Discharge counter

    Common anomalies:

    • Internal heating (degraded varistors)
    • Internal moisture
    • Inadequate ground connection

    Thermal pattern:

    • Normal: ambient temperature
    • Defect: localized or generalized heating

    Fault Patterns and Diagnosis

    Pattern 1: Loose Connection on a Busbar

    Symptoms:

    • Localized heating at a joint or connector
    • Possible visible discoloration or oxidation

    Causes:

    • Inadequate torque during installation
    • Mechanical vibration
    • Electrochemical corrosion
    • Differential thermal expansion

    Possible actions after technical confirmation:

    • Schedule a shutdown
    • Clean contact surfaces
    • Retighten to the specified torque
    • Apply conductive compound if necessary

    Pattern 2: Heated Transformer Bushing

    Symptoms:

    • Elevated temperature at the bushing
    • Progressive heating over time

    Causes:

    • Defective internal connection
    • Contamination of the insulating oil
    • Insulation degradation
    • Transformer overload

    Possible actions after technical confirmation:

    • Physicochemical analysis of the oil
    • Bushing power factor test
    • Consider replacement if a defect is confirmed
    • Reduce load if overload is identified

    Pattern 3: Tracking on an Insulator

    Symptoms:

    • Localized heating along a line or at a point
    • Possible visible carbon marks

    Causes:

    • Surface contamination (pollution, salt)
    • Moisture
    • Mechanical damage (crack)
    • Material aging

    Possible actions after technical confirmation:

    • Clean the insulator
    • Detailed visual inspection
    • Replace if structural damage is confirmed
    • Increase the frequency of preventive cleaning

    Pattern 4: Heating in a Circuit Breaker

    Symptoms:

    • Elevated temperature at the contacts
    • Asymmetric heating

    Causes:

    • Worn contacts
    • Oxidation
    • Mechanical misalignment
    • Inadequate contact pressure

    Possible actions after technical confirmation:

    • Contact resistance test
    • Mechanical inspection
    • Maintenance or replacement of contacts
    • Contact pressure adjustment

    Inspection Best Practices

    Planning

    1. Access authorization — permission to enter the substation

    2. Risk analysis — identify hazards and control measures

    3. Weather conditions — avoid rain, fog or strong wind

    4. Appropriate timing — a period of representative load

    5. Calibrated equipment — thermal camera and PPE

    Safety

    Plan access and risk controls according to the facility's procedure. Do not apply generic distances or PPE to a specific installation.

    During the Inspection

    1. Systematic scanning — follow a predefined route

    2. Multiple angles — capture different perspectives

    4. Record ambient temperature — for ΔT calculation

    5. Document the TAG — identification of each piece of equipment

    6. Note the load — current or power at the time of inspection

    After the Inspection

    1. Image analysis — identify thermal anomalies

    2. Calculate ΔT — determine severity

    3. Generate the report — include images, measurements and recommendations

    4. Prioritize actions — follow the severity criteria

    5. Inform operations — report critical anomalies immediately

    Conclusion

    Thermography in substations is an essential tool for predictive maintenance, making it possible to identify faults in transformers, busbars, insulators and other equipment before they escalate into supply interruptions. By following the safety best practices and severity criteria presented, it is possible to:

    • Reduce unplanned outages
    • Increase the reliability of the electrical system
    • Prevent damage to high-value equipment
    • Improve operational safety
    • Optimize maintenance costs

    Define the inspection frequency in the facility's maintenance plan, according to criticality, history and operating conditions.

    Assessment Criteria and Safety

    The priority of the finding must take into account load, manufacturer limits, measurement quality, thermal history and equipment criticality. Document the reference used for comparison and the technical justification for the proposed action. This article does not establish universal temperature ranges or repair deadlines.

    Brazilian regulatory standard NR-10 (the Brazilian occupational safety standard for electrical installations and services), in its text updated in 2019, item 10.2.1, requires preventive measures based on risk analysis for electrical interventions. Accessed on October 11, 2026.

    Sources

    Accessed on October 11, 2026.

    Share: